• ZR-BR-485-EM

Bridge ZigBee

Bridge ZigBee

SKU: ZR-BR-485-EM. Categories: , .

Product Description

Key features

  • Connecting Modbus devices to the ZigBee network
  • Using Modbus/RTU protocol and RS485 interface
  • Routing function
  • RF power 1mW
  • External antenna

How it works

The Bridge has the main function to connect through a ZigBee network one or more Modbus slave devices equipped with RS485 interface to one of the Gateways of the 4-noks products family. In this way the PLC or PC-SCADA connected to the Gateway can communicate with Modbus slave devices eliminating wire installation. This channel is completely transparent.
Furthermore it can be a repeater and a “parent” device for battery powered sensors.

Technical specs

General characteristics
Chip Ember EM2420
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Modbus/RTU
Radio characteristics Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 1mW (0 dBm)
Reception sensitivity: -92 dBm
Extern antenna Gain: 5,5 dB
Coverage outdoor/indoor: 100m/30m
Power supply 12-24 Vdc/Vac (±10%); 100mA; 50/60Hz
Connection Supply: pull out terminals (3,81 mm pitch)
RS-485 interface: extraction clamps (pitch 3.81 mm)
Environmental conditions Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
Degree of protection IP55
Conformity Community Directives 2006/95/CE, 89/336/EEC, 99/5/EEC; ETSI EN 300-328; ETSI EN 301-489; EN60950-1; EN50371; EN61000-6-2; EN 61000-6-3

Download