//, Smart Automation, ZigBee Home Automation/ZigBee 2 NTC Input and 2 Digital Input Module
  • ZED-TID-M

ZigBee 2 NTC Input and 2 Digital Input Module

ZigBee sensor

SKU: ZED-TID-M. Categories: , , .

Product Description

Key features

  • Input for two NTC temperature sensors (not included)
  • Two digital inputs
  • Alarm thresholds
  • Sampling and transmission rates are confi gurable
  • Battery powered
  • Long life battery
  • Internal antenna

How it works

The ZED-TID-M drill is a battery supplied device which can measure at the same time the temperature of 2 NTC sensors and the status of 2 digital input and regularly send the collected information toward a 4-noks range Gateway.
Is possible to set the device in order to manage alarms to ring when its limits are trespassed, because of a too high or too low temperature. The device can transmit automatically and immediately (out of the sampling time you have set up) also for a status change of one of the two input.

Technical specs

General characteristics
Chip Ember EM250
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Modbus/RTU
Address settable through internal dip-switch
Wall-mounting with screws
Cable gland: PG9
Radio characteristics Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 2mW (3 dBm)
Receiver sensitive: -95 dBm
Internal antenna gain: 0 dB
Outdoor/indoor range: 100m/30m
Power Supply High Energy Density AA 3,6V/2000mAh Lithium Battery
Battery duration: 3 years for data transmission every minute at 20°C
Inpur for NTC drill
NTC type drill
103AT Type (R25 = 10 KOhm; Beta = 3435K)
Measurement range: -50°C ÷ +100°C
Reading resolution: 0,1°C
Reading accuracy: ±1,0°C
Temperature measurements expressed as tenths of degree
Digital input
Non-isolated input for clean contact
Closure electrical current 0,01mA.
Use self cleaning contacts
Connection Plug off morsels (3,81 mm pitch)
Environmental parameters
Operating temperature: -10 ÷ +60°C; <80% U.R. non condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. non condensing
IP Protection IP55
Conformity Community Directives 2006/95/EEC, 89/336/EEC, 99/5/EEC
Product law applied: ETSI EN 300 328: Radio Compatibility for digital wide band transmissions; ETSI EN 301 489: Radio Compatibility; EN 61000-6-2: Electromagnetic Compatibility – Emissions; EN 61000-6-3: Electromagnetic Compatibility – Immunity; EN 60950-1: Electric Security

Download