Return to products >>
ZigBee S0 pulse counter
ZED-TIDCI-M
|
|

Key features
- 2 pulse counter inputs S0 compatible
- 2 thermal resistor inputs (NTC resistors not included)
- Sampling and transmission rates are confi gurable
- Battery powered
- Internal antenna
|
The ZED-TIDCI-M is a battery powered ZigBee device, capable to count pulses emitted from fl ow rate meters (water, gas, electricity,...) and to measure the temperature from both the 2 on board NTC inputs. Pulse counters and temperature samples are sent at regular intervals to a gateway of 4-noks products family.
Moreover, if temperature sensors are installed into an hydraulic circuit in the inlet and outlet pipes this device can General characteristicssend the difference between them.
|
Technical Specs
|
|
General characteristics
|
Chip Ember EM250
Compatible IEEE 802.15.4
Stack EmberZnet 3.5.x (ZigBee PRO)
Modbus/RTU
Device address settable via internal dip-switch
Wall mounting with screws
Cable gland: PG9
|
|
RF characteristics
|
Frequency: 2405 MHz ÷ 2480 MHz
Modulation: DSSS
Nominal transmission power: 2mW (3 dBm)
Reception sensitivity: -95 dBm
Internal antenna gain: 0 dB
Coverage outdoor/indoor: 100m/30m
|
|
Supply
|
AA high energy density lithium battery 3,6V/2000mAh
Battery life: 2 years in case of 1 transmission per minute at 20°C
|
|
NTC thermal resistor input
|
NTC type resistor
103AT type (R25 = 10 KOhm; Beta = 3435K)
Measurement range: -50°C ÷ +110°C
Measurement resolution: 0,1°C
Measurement accuracy : ±1,0°C
Measures are linearized at tenth of degree
|
|
Digital inputs
|
Electronic type not insulated inputs for clean contact
Short circuit current 0,01mA. Use self-cleaning contact
|
|
Connections
|
Pull out terminals (3,81 mm pitch)
|
|
Environment parameters
|
Operating temperature: -10 ÷ +60°C; <80% U.R. not condensing
Storage temperature: -20 ÷ +70°C; <80% U.R. not condensing
Degree of protection: IP 55
|
|
Compliant with 2006/95/EEC,
89/336/EEC, 99/5/EEC directives
Reference Norms
|
ETSI EN 300 328: Radio Compatibility for digitals wide band transmissions
ETSI EN 301 489: Radio Compatibility
EN 61000-6-2: Electromagnetic Compatibility - Emissions
EN 61000-6-3: Electromagnetic Compatibility - Immunity
EN 60950-1: Electric Safety
|
Download the Technical Sheet |
|
Request info
|
Print this page
|
|